| CVE |
Vendors |
Products |
Updated |
CVSS v3.1 |
| RuggedCom Rugged Operating System (ROS) before 3.3 has a factory account with a password derived from the MAC Address field in a banner, which makes it easier for remote attackers to obtain access by performing a calculation on this address value, and then establishing a (1) SSH or (2) HTTPS session, a different vulnerability than CVE-2012-1803. |
| The login implementation in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, has a hardcoded account, which makes it easier for remote attackers to obtain access via an unspecified request. |
| SQL injection vulnerability in the login screen in the Web Navigator in Siemens WinCC before 7.2 Update 1, as used in SIMATIC PCS7 8.0 SP1 and earlier and other products, allows remote attackers to execute arbitrary SQL commands via unspecified vectors. |
| Unspecified vulnerability in the client library in Siemens COMOS 9.2 before 9.2.0.6.10 and 10.0 before 10.0.3.0.4 allows local users to obtain unintended write access to the database by leveraging read access. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The implementation of SNMPv3 does not check the user credentials sufficiently. Therefore, an attacker is able to execute SNMP commands without correct credentials. |
| Cross-site scripting (XSS) vulnerability in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to inject arbitrary web script or HTML via unspecified vectors, a different vulnerability than CVE-2011-4511. |
| A vulnerability has been identified in SCALANCE X-200 switch family (incl. SIPLUS NET variants) (Versions < V5.0.0 for CVE-2013-3633 and versions < V4.5.0 for CVE-2013-3634), SCALANCE X-200IRT switch family (incl. SIPLUS NET variants) (All versions < V5.1.0). The user privileges for the web interface are only enforced on client side and not properly verified on server side. Therefore, an attacker is able to execute privileged commands using an unprivileged account. |
| Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to UDP port 161 (aka the SNMP port). |
| Siemens SIMATIC S7-1200 PLCs 2.x and 3.x allow remote attackers to cause a denial of service (defect-mode transition and control outage) via crafted packets to TCP port 102 (aka the ISO-TSAP port). |
| Directory traversal vulnerability in the web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote authenticated users to read arbitrary files via vectors involving a query for a pathname. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008; WinCC V11 (aka TIA portal); the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime has an improperly selected default password for the administrator account, which makes it easier for remote attackers to obtain access via a brute-force approach involving many HTTP requests. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly represent WebNavigator credentials in a database, which makes it easier for remote authenticated users to obtain sensitive information via a SQL query. |
| The web server in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to obtain sensitive information or cause a denial of service via a crafted project file. |
| RuggedCom Rugged Operating System (ROS) 3.10.x and earlier has a factory account with a password derived from the MAC Address field in the banner, which makes it easier for remote attackers to obtain access by performing a calculation on this address value, and then establishing a (1) TELNET, (2) remote shell (aka rsh), or (3) serial-console session. |
| Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, does not properly assign privileges for the database containing WebNavigator credentials, which allows remote authenticated users to obtain sensitive information via a SQL query. |
| The HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime generates predictable authentication tokens for cookies, which makes it easier for remote attackers to bypass authentication via a crafted cookie. |
| Buffer overflow in CCEServer (aka the central communications component) in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to cause a denial of service via a crafted packet. |
| Stack-based buffer overflow in the Profinet DCP protocol implementation on the Siemens Scalance S Security Module firewall S602 V2, S612 V2, and S613 V2 with firmware before 2.3.0.3 allows remote attackers to cause a denial of service (device outage) or possibly execute arbitrary code via a crafted DCP frame. |
| Buffer overflow in the RegReader ActiveX control in Siemens WinCC before 7.2, as used in SIMATIC PCS7 before 8.0 SP1 and other products, allows remote attackers to execute arbitrary code via a long parameter. |
| The HMI web application in Siemens WinCC (TIA Portal) 11 allows remote authenticated users to cause a denial of service (daemon crash) via a crafted HTTP request. |